微信公众号随时随地查标准

QQ交流1群(已满)

QQ群标准在线咨询2

QQ交流2群

购买标准后,可去我的标准下载或阅读

4.1 This test method is designed to present in a standardized format information on the variability of strength of cement from a single source over a period of time. It can be applied to all hydraulic cements covered in Specifications C150, C595, and C1157. The results derived from this test method are intended for information only and are not requirements of any existing ASTM specification. A specification may refer to this test method to obtain information on the variability of cement from a single source.4.2 The procedure is based on obtaining samples from locations during the delivery of cement to the user and is more representative of the variability of cement used in concrete production than test data reported on mill test reports. Variation determined from the test results is corrected for testing error, therefore giving the user one indicator of the source variation of the cement.NOTE 1: It should be recognized that concrete strength variability is influenced by other factors in addition to cement strength variability.4.3 This test method does not provide information on the relationship between the variability of cement and the variability of concrete properties. The user can, along with supplementary information or correlative testing of concrete properties, develop quantitative estimates of the effects.1.1 This test method covers a procedure for determining the variability of a hydraulic cement produced at a single source using strength tests as the characteristic property. It is intended that this test method normally be used for the predominant cement manufactured at a cement plant. Guidelines for sampling, testing, presentation of results, and evaluation are given.1.2 The values stated in either SI units or inch-pound units are to be regarded separately as the standard. The values stated in each system may not be exact equivalents; therefore each system shall be used independently of the other. Combining values from the two systems may result in non-conformance with the standard. One system of units is used in the Figure and Tables in this standard to illustrate the calculation methods that are applicable independent of the system of units.1.3 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory limitations prior to use.1.4 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.

定价: 590元 / 折扣价: 502 加购物车

在线阅读 收 藏

1.1 This specification covers requirements for metric series, tapered roller bearings with a single row of rollers.1.2 Intended Use—The bearings covered in this specification are intended to be used in general industrial and vehicle applications where the operating temperature does not exceed 120 °C (250 °F).1.3 This specification contains many of the requirements of DS3225, which was originally developed by the Department of Defense and maintained by the Defense Supply Center in Richmond. The following government activity codes may be found in the Department of Defense, Standardization Directory SD-1.2Preparing Activity Custodians Review ActivitiesDLA-GS4 Army-AT Army-AV  Navy-MC Navy –MC, SH  Air Force-99 Air Force-84    Other-NS1.4 The values stated in SI units are to be regarded as standard. No other units of measurement are included in this standard.1.5 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory limitations prior to use.1.6 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.

定价: 590元 / 折扣价: 502 加购物车

在线阅读 收 藏
ASTM D4975-14 Standard Test Methods for Single-Filament Tire Bead Wire Made from Steel (Withdrawn 2023) Withdrawn, No replacement 发布日期 :  1970-01-01 实施日期 : 

5.1 The procedures for the determination of properties of single-filament bead wire made from steel are considered satisfactory for acceptance testing of commercial shipments of this product because the procedures are the best available and have been used extensively in the trade.5.1.1 In case of a dispute arising from differences in reported test results when using these test methods for acceptance testing of commercial shipments, the purchaser and supplier should conduct comparative test to determine if there is a statistical bias between their laboratories. Competent statistical assistance is recommended for the investigation of bias. As a minimum, the two parties should take a group of test specimens which are as homogeneous as possible and which are from a lot of material of the type in question. The test specimens then should be randomly assigned in equal number to each laboratory for testing. The average results from the two laboratories should be compared using Student's t-test for unpaired data and an acceptable probability level chosen by the two parties before testing is begun. If a bias is found, either its cause must be determined and corrected or the purchaser and the supplier must agree to interpret future test results with consideration to the known bias.1.1 These test methods cover testing of single-filament steel wires that are components of tire beads used in the manufacture of pneumatic tires. By agreement, these test methods may be applied to similar filaments used for reinforcing other rubber products.1.2 These test methods describe test procedures only and do not establish specifications and tolerances.1.3 The values stated in SI units are to be regarded as standard. No other units of measurement are included in this standard.1.4 These test methods cover the determination of the mechanical properties listed below:  Property   Section   Breaking Force (Strength)  7 – 13  Yield Strength  7 – 13  Elongation  7 – 13  Torsion Resistance 14 – 20  Diameter (Gage) 21 – 271.5 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use.

定价: 0元 / 折扣价: 0

在线阅读 收 藏

5.1 This test method is intended to generate an extract with a concentration of the target analyte(s) representative of the expected release under the scenario simulated, and which can be compared with concentration levels acceptable in waste disposal, treatment, or production activities.5.2 The extraction conditions of the test method were chosen to simulate a potential disposal scenario to which the wastes may be exposed.5.3 One intent of this test method is that the amount of acid in the extraction fluids reflects the acid available from the leachate of a specific landfill where municipal and industrial wastes were co-disposed.65.4 One intent of this test method is to not allow the pH of the extraction fluid to be lower than that of the leachate of a specific landfill where municipal and industrial wastes were co-disposed. Therefore, the pH of the extraction fluid was chosen with the following considerations:(1) Not to be less than 4.93 ± 0.05 for the extraction of wastes with an acid neutralization capacity of less than the acid available in the total volume of extraction fluid used in the method (Extraction Fluid No. 1).(2) At 2.88 ± 0.05, as defined by the pH of the acid, for the extraction of wastes with an acid neutralization capacity of more than the acid available in the extraction fluid used in the method (Extraction Fluid No. 2).5.5 The interpretation and use of the results of this test method are limited by the assumptions of a single co-disposal scenario and by the factors affecting the composition of a landfill leachate and chemical or other differences between a selected extraction fluid and the real landfill leachate.5.6 This test method may be affected by biological changes in the waste, and it is not designed to isolate or measure the effect of such processes.5.7 This test method produces extracts that are amenable to the determination of both minor and major constituents. When minor constituents are being determined, it is especially important that precautions be taken in sample storage and handling to avoid possible contamination of the samples.5.8 The agitation technique, rate, liquid-to-solid ratio, and filtration conditions specified in the method may not be suitable for extracting all types of wastes.5.9 This test method is intended to extract the samples in their original physical state as is, without any size reduction. However, the sample/extractor interaction is expected to correlate with the environmental conditions to which a waste may be exposed.75.10 The extraction conditions defined by this test method are expected to yield steady-state concentrations, determined by the extraction liquid-to-solid ratio and the duration of the extraction, which may or may not agree with the concentration of an equilibrium.1.1 This test method is applicable to the extraction of samples of treated or untreated solid wastes or sludges, or solidified waste samples, to provide an indication of the leaching potential.1.2 This test method is intended to provide an extract for measurement of the concentration of the analytes of concern. The measured values may be compared against set or chosen acceptance levels in some applications.1.3 If the sole application of the test method is such a pass/fail comparison and a total analysis of the waste demonstrates that individual analytes are not present in the waste, or that the chosen acceptance concentration levels could not possibly be exceeded, the test method need not be run.1.4 If the sole application of the test method is such a pass/fail comparison and an analysis of any one of the liquid fractions of the extract indicates that the concentration of the target analyte is so high that, even after accounting for dilution from the other fractions of the extract, it would be equal to or above an acceptance concentration level, then the waste fails the test. In such a case it may not be necessary to analyze the remaining fractions of the extract.1.5 This test method is intended to provide an extract suitable for the measurement of the concentration of analytes that will not volatilize under the conditions of the test method.1.6 Presence of volatile analytes may be established if an analysis of the extract obtained using this test method detects the target volatile analyte. If its concentration is equal to or exceeds an acceptance level for that analyte, the waste fails the test. However, extract from this test method shall not be used to determine the concentration of volatile organic analytes.1.7 This test method is intended to describe only the procedure for performing a batch extraction. It does not describe all of the sampling and analytical requirements that may be associated with the application of this test method.1.8 The values stated in either SI or inch-pound units are to be regarded as the standard. The values given in parentheses are for information only.1.9 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory limitations prior to use. For a specific precautionary statement, see Note 8.1.10 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.

定价: 590元 / 折扣价: 502 加购物车

在线阅读 收 藏

4.1 This practice is designed to present in a standardized format information on the variability of limestone or lime from a single source over a period of time. It can be applied to all materials covered in Test Methods C25, C110, C1271, and C1301, and Specification C141.1.1 This practice is intended for use in instances where the purchaser desires information on the uniformity of limestone or lime produced at a single source. It is intended that this test method normally be used for the predominant material manufactured at a plant. Guidelines for sampling, testing and presentation of results (Table 1) are given.1.2 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory limitations prior to use.1.3 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.

定价: 515元 / 折扣价: 438 加购物车

在线阅读 收 藏

This specification covers aluminum 1350-H19, 1350-H16 or -H26, 1350-H14 or -H24, 1350-H142 or -H242, and aluminum alloy 8XXX series for tempers "O" and H1X or H2X, bare stranded conductors composed of one or more roller shaped or die compressed layers of helically laid wires. The conductors are for general use for electrical purposes. The conductors described in this specification are intended for subsequent insulation or covering. The areas of cross section, the minimum number of wires, and diameters of the finished strand shall conform to the prescribed construction requirements. The rated strength of 1350-H19 conductors shall be taken as the percent of the sum of the strengths of the component wires, calculated using the nominal wire diameters and the specified minimum average tensile strength. The rated strength of 800 series conductors shall be taken as the percent of the sum of strengths of the component wires, calculated using nominal wire diameters and the specified minimum average tensile strength. The approximate mass and electrical resistance may be determined using the standard increments due to stranding. Mechanical and electrical tests shall be made for not annealed and annealed conductors after stranding. Temperature correction factors for conductor resistance shall be provided when dc resistance is measured at specified temperatures.1.1 This specification covers aluminum 1350-H19 (extra hard), 1350-H16 or -H26 (3/4 hard), 1350-H14 or -H24 (1/2 hard), 1350-H142 or -H242 (1/2 hard), and aluminum alloy 8XXX series as listed in Specification B800 for tempers “O” and H1X or H2X, bare stranded conductors composed of one or more roller shaped or die compressed layers of helically layed wires. The conductors are for general use for electrical purposes (Explanatory Notes 1 and 2).NOTE 1: For the purposes of this specification, single input wire (SIW) construction is defined as follows: a stranded conductor design methodology that varies the number of wires within a range of conductor sizes in order to permit that range of conductor sizes to be constructed from a single wire size.1.2 The SI values for resistivity are regarded as standard. For all other properties, the inch-pound units are regarded as standard and the SI units may be approximate.NOTE 2: Prior to 1975, aluminum 1350 was designated as EC aluminum.NOTE 3: The aluminum and temper designations conform to ANSI H35.1. Aluminum 1350 corresponds to Unified Numbering System A91350 in accordance with Practice E527. Aluminum alloys in the 8000 series correspond to Unified Numbering System A98XXX in accordance with Practice E527.NOTE 4: This specification also permits conductors for use as covered or insulated electrical conductors.NOTE 5: Sealed conductors, which are intended to prevent longitudinal water propagation and are further covered/insulated, are also permitted within the guidelines of this specification.1.3 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.

定价: 590元 / 折扣价: 502 加购物车

在线阅读 收 藏

This specification covers stranded conductors made from round copper wires, either uncoated or coated with tin, lead, or lead alloy for general use in insulated conductor assemblies for electrical purposes. These conductors shall be composed of one or more roller shaped or die closed layers of helically laid wires using the single input wire. For stranded conductors, the direction of lay of the outer layer shall be leeft hand and may be reversed or unidirectional/unilay in successive layers. Test for the physical and electrical properties of wires composing conductors made from hard-drawn or medium-hard-drawn wires, uncoated or coated, shall be made before but not after stranding. For the purpose of calculating mass, cross sections, and so forth, the density of the copper shall be taken. The mass and electrical resistance of a unit length of stranded unsealed conductor are a function of the lenght of lay shall be calculated.1.1 This specification covers stranded conductors made from round copper wires, either uncoated or coated with tin, lead, or lead alloy for general use in insulated conductor assemblies for electrical purposes. These conductors shall be composed of one or more roller shaped or die closed layers of helically laid wires using the single input wire (SIW) methodology. (see Note 1 and Explanatory Note 1)NOTE 1: Sealed conductors which are intended to prevent longitudinal water propagation and are further covered/insulated, are also permitted within the guidelines of this specification.1.2 The values stated in inch-pound or SI units are to be regarded separately as standard. The values in each system are not exact equivalents; therefore, each system shall be used independently of the other. Combining values from the two systems may result in nonconformance with the specification.1.2.1 For density, resistivity, and temperature, the values stated in SI units are to be regarded as standard.1.3 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.

定价: 590元 / 折扣价: 502 加购物车

在线阅读 收 藏

5.1 Uranium hexafluoride is a basic material used to produce nuclear reactor fuel. To be suitable for this purpose, the material must meet criteria for isotopic composition. This test method is designed to determine whether the material meets the requirements described in Specifications C787 and C996.1.1 This test method is applicable to the isotopic analysis of uranium hexafluoride (UF6) with 235U concentrations less than or equal to 5 % and  234U,   236U concentrations of 0.0002 to 0.1 %.1.2 This test method may be applicable to the analysis of the entire range of  235U isotopic compositions providing that adequate Certified Reference Materials (CRMs or traceable standards) are available.1.3 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory limitations prior to use.1.4 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.

定价: 515元 / 折扣价: 438 加购物车

在线阅读 收 藏

5.1 The procedures for the determination of properties of single-filament hose reinforcing wire made from steel are considered satisfactory for acceptance testing of commercial shipments of this product because the procedures are the best available and have been used extensively in the trade.5.1.1 In the case of a dispute arising from differences in reported test results when using these test methods for acceptance testing of commercial shipments, the purchaser and supplier should conduct comparative tests to determine if there is a statistical bias between their laboratories. Competent statistical assistance is recommended for investigation of bias. As a minimum, two parties should take a group of test specimens which are as homogeneous as possible and which are from a lot of material of the type in question. The test specimens then should be randomly assigned in equal numbers to each laboratory for testing. The average results from the two laboratories should be compared by using an appropriate statistical test and an acceptable probability level chosen by the two parties before testing is begun. If a bias is found, either its cause must be determined and corrected or the purchaser and supplier must agree to interpret future test results with consideration to the known bias.1.1 These test methods cover testing of single filament steel wires that are used to reinforce hose products. By agreement, these test methods may be applied to similar filaments used for reinforcing other rubber products.1.2 These test methods describe test procedures only and do not establish specifications or tolerances.1.3 These test methods cover the determinations of the mechanical properties listed below:  Property Section  Breaking force (strength)  7 – 13  Yield strength  7 – 13  Elongation  7 – 13  Knot strength 14 – 20  Torsion resistance 21 – 27  Reverse bend 28 – 34  Wrap 35 – 41  Diameter 42 – 481.4 The values stated in either SI units or inch-pound units are to be regarded separately as standard. The values stated in each system may not be exact equivalents; therefore, each system shall be used independently of the other. Combining values from the two systems may result in non-conformance with the standard.1.5 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use.

定价: 0元 / 折扣价: 0

在线阅读 收 藏

4.1 This practice provides a systematic procedure for sampling and determining the variability of user-selected properties of concrete-making materials. Results derived from application of the practice are generally intended for information only and are not requirements of any existing ASTM specification on concrete or concrete-making materials. A concrete materials specification may make reference to this practice as a means of obtaining variability information, but needs to define the properties to be measured and the lot size and sample unit to be used. This practice is applicable to both producers and consumers of concrete-making materials, although details of application of the practice may vary, depending on the intended purpose of the user of this practice.4.2 The procedure is applicable to any quantitative property of any concrete-making material that can be measured by a standard test method. The procedure is based on grab samples, which will tend to show the maximum amount of variation of the material being evaluated. The procedure is useful if grab samples are obtained from sampling units that are being delivered to the user of a material and better represents the variability of the material used in concrete production than tests performed on the material for specification compliance that are documented on a mill test report or material certification. The procedure was developed for application to materials from a single source, but it can be applied to a materials delivery stream from more than one source, depending on the purposes of the user of the practice. Variations among test results on separate samples within a lot are corrected for testing error, therefore giving an estimate of the variability of the selected material property. The variability of the selected material property provides the user with one indicator of the source variation of the concrete-making material.4.3 Although variability in properties of concrete-making materials can be a significant cause of variability in concrete properties, this practice does not purport to give information on this relationship. This practice does give information on variability of concrete-making materials from which the user can, along with supplementary information or correlative testing of concrete properties, develop quantitative estimates of the effects.1.1 This practice covers a procedure for determining the variability of concrete-making materials from a single source by measuring a characteristic property of the material. It includes recommendations on sampling, testing, analysis of data, and reporting.1.2 The system of units for this practice is not specified. Units used in examples of calculation methods are for illustration purposes. The calculation methods described in this practice can be used with either SI or inch-pound units.1.3 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory limitations prior to use.1.4 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.

定价: 590元 / 折扣价: 502 加购物车

在线阅读 收 藏

5.1 The measurement of total moisture is required to determine whether coal meets commercial or environmental specifications, or both. Within the limitations prescribed in the scope, this practice describes a procedure for determination of total moisture that requires less time than the procedures described in Test Method D3302/D3302M.1.1 This practice covers a single-stage procedure for the determination of total moisture less than 15 % in coal reduced to 2.36 mm [No. 8 sieve] topsize. This practice is for determination of total moisture only. Materials subjected to this test shall not be used in the determination of other test parameters. It is recognized that the conditions of the test can increase the potential for significant oxidation effects on some coals. If the oxidation potential is of concern, the use of this single-stage method shall involve prior agreement between the parties involved. This practice shall not be construed as the referee standard practice for total moisture. For referee purposes, users of this practice are referred to Test Method D3302/D3302M for moisture determination methods which are not as susceptible to oxidation effects.1.2 Statistical analysis of data from several sources indicates that at a 95 % confidence level, there is statistically no difference between the mean value of the results obtained by Practice D2961/D2961M and Test Method D3302/D3302M (that is, no bias is detected between the two methods at the 95 % confidence level) for moisture levels between 1.4 % and 15.8 %. These two standards were not compared in this study for some ranks of coal including lignite and anthracite.21.3 The values stated in either SI units or inch-pound units are to be regarded separately as standard. The values stated in each system are not necessarily exact equivalents; therefore, to ensure conformance with the standard, each system shall be used independently of the other, and values from the two systems shall not be combined.1.4 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory limitations prior to use.1.5 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.

定价: 515元 / 折扣价: 438 加购物车

在线阅读 收 藏

This specification covers fiber or fabric reinforced non-vulcanized polymeric sheet made from chlorosulfonated polyethylene (CSM) intended for use as a single-ply roof membrane exposed to the weather. In-place roof systems design criteria such as fire resistance, field seaming strength, impact/puncture resistance, material compatibility, and uplift resistance, among others, are beyond the scope of this specification. Backed or reinforced sheets shall conform to the following physical properties: thickness; breaking strength; elongation; tearing strength; low temperature bend; linear dimensional change; ply adhesion; hydrostatic resistance; ozone resistance; and weather resistance. On the other hand, coating portions on the weather side of the sheet containing neither backing nor internal reinforcement shall adhere to the following physical properties: tensile strength; elongation; tear resistance; ozone resistance; and water absorption.1.1 This specification covers reinforced non-vulcanized polymeric sheet made from chlorosulfonated polyethylene (CSM) (see Note 1 ) intended for use as a single-ply roof membrane exposed to the weather. The sheet shall be reinforced with fiber or fabric.Note 1The term CSPE for chlorosulfonated polyethylene is commonly used in the roofing industry.1.1.1 The polymers used in these sheets have thermoplastic characteristics at time of installation. The chlorosulfonated polyethylene will vulcanize in place under ambient conditions.1.2 The tests and property limits used to characterize these sheets are minimum values.1.2.1 In-place roof systems design criteria such as fire resistance, field seaming strength, impact/puncture resistance, material compatibility, and uplift resistance, among others, are factors that must be considered, but are beyond the scope of this specification.1.3 The values stated in SI units are to be regarded as the standard. The values given in parentheses are for information only.1.4 The following precautionary caveat pertains to the test methods portion only, Section 8, of this specification: This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use.

定价: 0元 / 折扣价: 0

在线阅读 收 藏

This specification covers the general requirements and test methods for materials, dimensions, workmanship, elongation, brittleness, pipe stiffness, and markings for single wall corrugated polypropylene (PP) pipe and fittings used in non-pressure gravity applications, including leach field effluent disposal, and drainage applications such as land, roads, foundations, agricultural, and landfill. It applies to PP corrugated single wall pipe and fittings with nominal sizes 3 in. through 30 in. (75 mm through 750 mm). This specification includes minimum properties for PP compounds used in the manufacture of corrugated single wall pipes, as well as nominal pipe sizes, inside diameters and tolerances for single wall corrugated PP pipes. It also covers fittings and joining system requirements, installation requirements, sampling and retest, certification, reporting, packaging, and quality assurance.1.1 This specification covers requirements and test methods for materials, dimensions, workmanship, elongation, brittleness, pipe stiffness, and markings for single wall corrugated polypropylene (PP) pipe and fittings. It covers nominal sizes 3 in. through 30 in. (75 mm through 750 mm)1.2 The corrugated polypropylene pipe and fittings are for use in non-pressure applications where soil-tight joints are acceptable, such as leach field effluent disposal, and drainage applications such as land, roads, foundations, agricultural, and landfill. Products meeting this specification are not suitable for applications requiring water-tight joints unless the manufacturer offers such joints as an option.NOTE 1: Watertight joints, when requested or specified, should meet a 10.8 psi (74 kPa) laboratory internal and external pressure in accordance with Specification D3212 and should utilize a bell and spigot design with a gasket that complies with Specification F477.1.3 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical conversions to SI units that are provided for information only and are not considered standard.1.4 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory limitations prior to use.1.5 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.

定价: 590元 / 折扣价: 502 加购物车

在线阅读 收 藏

4.1 This practice provides a guide for the evaluation of shipping units in accordance with a uniform system, using established test methods at levels representative of those occurring in actual distribution. The recommended test levels are based on available information on the shipping and handling environment, and current industry/government practice and experience. The tests should be performed sequentially on the same containers in the order given. For use as a performance test, this practice requires that the shipping unit tested remain unopened until the sequence of tests are completed. If used for other purposes, such as package development, it may be useful to open and inspect shipping units at various times throughout the sequence. This may, however, prohibit evaluating the influence of the container closure on container performance.1.1 This practice provides a uniform basis of evaluating, in a laboratory, the ability of shipping units, weighing up to but not exceeding 150 lb (68 kg), intended for the single parcel delivery system to withstand the hazards associated with the distribution environment. This is accomplished by subjecting them to a test plan consisting of a sequence of anticipated hazard elements encountered in the distribution cycles. This practice is not intended to supplant material specifications or existing pre-shipment test procedures.1.2 The suitability of this practice for use with hazardous materials has not been determined.1.3 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical conversions to SI units that are provided for information only and are not considered standard.1.4 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use. Specific precautionary statements are given in 1.1.

定价: 590元 / 折扣价: 502 加购物车

在线阅读 收 藏

4.1 This guide and the use of consensus performance standards for housing can significantly contribute to the removal of barriers to the acceptance of housing innovation in the global marketplace. This guide in conjunction with the balance of the set of standard guides can also serve to improve communications between producers and consumers leading to enhanced quality and performance of housing.4.2 This guide is not intended for use in specifying and evaluating residential construction other than single family attached and detached dwellings.4.3 Although this guide addresses site planning as it affects functionality of single family attached and detached dwellings, the site-planning issues considered are not be construed as a comprehensive site specification.4.4 This guide can be useful to managers of housing procurement projects, home builders, designers, product manufacturers, and evaluation services in addressing functionality issues related to single family attached and detached dwellings. Such applications can require that the examples of performance statements be written in mandatory language.4.5 Methodology/Special Conditions:4.5.1 In order to provide the specifier added flexibility in the choice of specific building elements, the specifier may choose to require that the providers submit information on certain building elements representing alternative levels of quality, beyond those which are defined by the attributes in the complete set of standard guides. For each of these the providers should be required to submit details, specifications, or other appropriate information as determined by the specifier.4.5.2 Some elements that may need these alternatives are finishes, fixtures and hardware.4.6 Code Compliance—This guide does not intend to take precedence over applicable standards, federally regulated standards local rules, codes and regulations.4.7 Data and Dimensions:4.7.1 Anthropometric—The specifier should provide the potential providers with important dimensions such as the height, width, reach, stretch, eye level of potential occupants standing and sitting, as well as other relevant anthropometric dimension so the occupants can conveniently use the dwelling unit. The Specifier should take into consideration occupants who do not fit into the population mean; the dimensions should be adjusted as required. See the standard Guide “I”—Accessibility for Dimensions Associated with Access for the Disabled.4.7.1.1 Discussion—The 97.5 percentile (large male) dimensions may be used to determine space envelopes, the 2.5 percentile (small person) may be used to determine the maximum reach areas by hand or foot, and the 50 percentile (average person) may be used to establish control and display heights. Reference: “Humanscale 7/8/9” (see Section 2).4.7.2 Furniture Sizes—The specifier may provide potential providers with typical furniture dimensions that will be used in conjunction with the performance statements that address furnishability to evaluate the appropriateness of room shapes and layouts. Providers wishing to suggest other furniture types for the purpose of evaluation should provide justification, dimensions, and documentation that a variety of each of these furniture types to be substituted is readily available. Reference: Residential chapter of “Time-Saver Standards For Building Types,” Residential Furnishings section of “Architectural Graphic Standards” (see Section 2).4.7.3 Movement and Circulation Minima—See the Ease of Movement Performance Statements, in Appendix X2 for minimum movement and circulation. Where such movement and circulation conditions exist, the guidelines are intended to be used with the furniture size information (see 4.7.2) and with the furnishability criteria in section X2.2.3 and the Performance Statements in Appendix X2. The specifier may choose to modify and add to these minimum guidelines based on project specific objectives. Providers wishing to use alternative minimum circulation dimensions should be required to provide documentation from a source acceptable to the specifier indicating that the intended dimensions are adequate. Also, where the specifier has included accessibility considerations see ASTM Designation: I-__ Pre-Standard Guide for Specifying and Evaluating Performance of Single Family Attached and Detached Dwellings—Accessibility.4.8 Provisions for a Functional Building Site—See Section 6.4.8.1 Site Planning—See Section 6.4.9 Automobile Parking—See Section 6.1.1 This guide provides examples of performance statements for functional and operable, spaces, products, components, and subsystems for single family attached and detached dwellings. These include the location, relationships, and dimensions of Spaces and Fittings, Furnishings and Equipment, and the operability and other parameters of Functionality of the Exterior Enclosure, Interior Space Division, Plumbing, HVAC, Fire Protection Subsystems, Electrical Network, Communication and Security Networks, Fuel Networks and Fittings, and Furnishings and Equipment that are not covered by the performance statements of the other attributes. See Fig. 1, Matrix of Parameters of Functionality.FIG. 1 Matrix of Parameters of Functionality1.2 The values stated in SI units are to be regarded as standard. The values given in parentheses are mathematical conversions to inch-pound units that are provided for information only and are not considered standard.1.3 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory requirements prior to use.

定价: 0元 / 折扣价: 0

在线阅读 收 藏
108 条记录,每页 15 条,当前第 1 / 8 页 第一页 | 上一页 | 下一页 | 最末页  |     转到第   页