This standard applies to voltage-endurance testing of form-wound stator winding bars and coils having a mica-based insulation system with theremo-setting polyester and/or epoxy resins used in hydrogenerators and pumped storage generators operating in air with a rated line-to-line voltage between 4 000 to 22 000 V, and a frequency of 50 Hz or 60 Hz.
This recommended practice covers the voltage endurance testing of form-wound bars and coils for use in large rotating machine stator windings. Such testing is defined for machines with a nominal voltage rating up to 30 000 V. These tests are to be applied at 50 Hz or 60 Hz and may be done at either room temperature or elevated temperature. (Testing at 50 Hz or 60 Hz may yield different times to failure for comparable samples.) The specimen to be tested should be representative of the bars or coils used in the machine, and should include the complete insulated bar and external grading construction that the machine winding would have. Special features different than those used in the machine should not be added to the test specimens.
This standard applies to voltage-endurance testing of form-wound stator winding bars and coils having a mica-based insulation system with theremo-setting polyester and/or epoxy resins used in hydrogenerators and pumped storage generators operating in air with a rated line-to-line voltage above 4000 V and a frequency of 50 Hz or 60 Hz.